Disclaimer – general guide only. These fault codes and diagnostic steps are compiled from manufacturer documentation and field experience for reference only. Code meanings can differ between models, series, software versions and regions, so always confirm against the manufacturer’s service manual or the information on the unit. Refrigerant, electrical and gas work must only be carried out by appropriately licensed technicians (ARCtick refrigerant licence and Queensland electrical licence). Isolate power before opening any unit. Total Cooling Services Qld accepts no liability for any loss, damage or injury arising from the use of this information. Need a hand? Call 07 3112 7566.

Full searchable version with diagnostic procedures: totalcoolingservices.com.au/fault-code-finder

Always confirm against the service manual for the exact model before replacing parts. Compiled 20 Nov 2026 from manufacturer service documentation and Carrier/Toshiba Australia fault code sheets.

DAIKIN

Residential split, multi & domestic ducted (R-32 / R-410A)

Models: FTXM, FTKM, FTXZ, FTXJ, FTXV, FTXF, FTXS, FTXP, FTXR, FTKF, FVXM, FVXS, FDYQ, FDXM, FDMRN, FFA, FCAG, MXM, MXS, RXM, RXZ, RXV, RXF, RXJ, RZQ, RXP, CTXM, Alira, Cora, Zena, US7, Lite, Emura

How to read: On the Daikin wireless remote, press and hold CANCEL (or TEMP ▼ on some remotes) for ~5 seconds until '00' flashes. Press CANCEL repeatedly to step through codes; a long beep (and steady operation lamp) identifies the stored code. Wired controllers display the code directly. Detailed sub-codes (e.g. A1-00, L5-00) appear on newer units.

  • 00 – Normal — no fault
  • A1 – Indoor PCB abnormality
  • A3 – Drain level control system abnormality (ducted/cassette)
  • A5 – Freeze-up protection (cooling) / high pressure control (heating)
  • A6 – Indoor fan motor abnormality / lock
  • AH – Streamer / air purifier unit abnormality
  • C4 – Indoor heat exchanger (liquid pipe) thermistor abnormality
  • C7 – Front panel / louvre limit switch abnormality
  • C9 – Indoor room (suction air) thermistor abnormality
  • CC – Humidity sensor abnormality
  • E1 – Outdoor PCB abnormality
  • E3 – High pressure protection (HPS activated)
  • E5 – Compressor overload (OL activation) / compressor overheat
  • E6 – Compressor lock / start-up failure
  • E7 – Outdoor DC fan motor lock
  • E8 – Input overcurrent detected
  • E9 – Electronic expansion valve (EEV) abnormality
  • EA – Four-way valve abnormality
  • F3 – Discharge pipe temperature too high
  • F6 – High pressure control in cooling / refrigerant overcharge
  • H0 – Compressor sensor system abnormality
  • H6 – Compressor position detection sensor abnormality
  • H8 – Current transformer (CT) / DC current sensor abnormality
  • H9 – Outdoor air thermistor abnormality
  • J3 – Discharge pipe thermistor abnormality
  • J6 – Outdoor heat exchanger thermistor abnormality
  • J8 – Liquid pipe thermistor abnormality (multi)
  • J9 – Gas pipe thermistor abnormality (multi)
  • L3 – Electrical box temperature rise
  • L4 – Inverter radiation fin (heatsink) temperature rise (Check outdoor airflow and heatsink contact)
  • L5 – Inverter output overcurrent
  • P4 – Radiation fin (heatsink) thermistor abnormality
  • U0 – Refrigerant shortage
  • U2 – DC voltage drop / main circuit overvoltage
  • U4 – Transmission error between indoor and outdoor unit
  • U7 – Transmission error between outdoor PCBs
  • UA – Incorrect indoor/outdoor combination / unspecified voltage
  • UH – Anti-icing (other rooms) / unspecified unit — multi systems

SkyAir & VRV commercial (wired controller BRC)

Models: FBA, FCA, FCQ, FFQ, FHA, FAA, FXFQ, FXSQ, FXMQ, FXAQ, FXZQ, FXDQ, RZA, RZAS, RZASG, RZQG, RXYQ, REYQ, RXYSQ, BRC1, BRC2, BRC4, Madoka

How to read: Codes show on the BRC wired controller. On Madoka (BRC1H) and Navigation (BRC1E) press the menu/info button to view the error and its sub-code and history. Outdoor PCB 7-segment display on VRV gives detailed codes.

  • A0 – External protection device activated
  • A1 – Indoor PCB defect
  • A3 – Drain level control system abnormality
  • A5 – Freeze-up / high pressure control
  • A6 – Indoor fan motor lock / overload
  • A7 – Swing flap motor abnormality
  • A9 – Indoor EEV abnormality
  • AF – Drain level above limit / humidifier
  • AJ – Capacity setting abnormality
  • C4 – Indoor liquid pipe thermistor
  • C5 – Indoor gas pipe thermistor
  • C9 – Indoor return air thermistor
  • CJ – Remote controller thermistor
  • E1 – Outdoor PCB defect
  • E3 – High pressure switch activated
  • E4 – Low pressure abnormality
  • E5 – Compressor motor lock / overload
  • E6 – Compressor overcurrent / lock
  • E7 – Outdoor fan motor abnormality
  • E9 – Outdoor EEV abnormality
  • F3 – Discharge pipe temperature abnormality
  • F6 – Refrigerant overcharge
  • H3 – High pressure switch abnormality
  • H7 – Outdoor fan motor signal abnormality
  • H9 – Outdoor air thermistor
  • J3 – Discharge pipe thermistor
  • J5 – Suction pipe thermistor
  • J6 – Outdoor heat exchanger thermistor
  • J7 – Outdoor liquid pipe thermistor
  • JA – High pressure sensor abnormality
  • JC – Low pressure sensor abnormality
  • L1 – Inverter PCB abnormality
  • L4 – Inverter heatsink temperature rise
  • L5 – Inverter compressor instantaneous overcurrent
  • L8 – Inverter compressor overcurrent (electronic thermal)
  • L9 – Inverter compressor start-up failure (stall prevention)
  • LC – Transmission between outdoor control PCB and inverter PCB
  • P1 – Inverter over-ripple / open phase / power imbalance
  • P4 – Inverter heatsink thermistor
  • PJ – Capacity setting mismatch (outdoor)
  • U0 – Refrigerant shortage / low pressure drop
  • U1 – Reverse phase / open phase
  • U2 – Power supply voltage insufficient / abnormal
  • U3 – Check operation not completed
  • U4 – Indoor–outdoor transmission error
  • U5 – Remote controller–indoor transmission error
  • U7 – Outdoor–outdoor transmission / cool-heat selector error
  • U8 – Main–sub remote controller transmission error
  • U9 – Transmission error with other indoor unit in system
  • UA – Indoor/outdoor/controller combination error
  • UC – Central control address duplication
  • UE – Transmission error with central controller
  • UF – Refrigerant system not set / wiring–piping mismatch
  • UJ – Accessory device transmission error

MITSUBISHI ELECTRIC

Mr Slim commercial & wall/ducted (PEA, PLA, PKA, PCA, SEZ, SLZ, PEAD, MSZ check mode)

Models: PEA, PEAD, PEY, PLA, PKA, PCA, SEZ, SLZ, PUZ, PUHZ, SUZ, MSZ, MXZ, MUZ, PAR-, PAR-33, PAR-41, PAR-40

How to read: Wired controller (PAR-xx): code shows on screen; press CHECK twice for self-diagnosis history. Wireless remote: press CHECK twice, point at the unit and press TEMP up/down — the beeper/OPERATION lamp blinks a number of times; the count gives the check code below (Pattern A = indoor detected, Pattern B = outdoor detected). MSZ wall splits use the same check-code family; blink-counts can differ slightly by model.

  • P1 – Intake (return air) sensor error (Pattern A — 1 blink)
  • P2 – Pipe (liquid, TH2) sensor error (Pattern A — 2 blinks)
  • P9 – Pipe (2-phase, TH5) sensor error (Pattern A — 2 blinks)
  • E6 – Indoor/outdoor communication error (indoor detected) (Pattern A — 3 blinks)
  • E7 – Indoor/outdoor communication error (Pattern A — 3 blinks)
  • P4 – Drain sensor error / float switch connector open (Pattern A — 4 blinks)
  • P5 – Drain pump error (Pattern A — 5 blinks)
  • PA – Forced compressor stop (water leakage abnormality) (Pattern A — 5 blinks)
  • P6 – Freezing / overheating protection operation (Pattern A — 6 blinks)
  • EE – Communication error between indoor and outdoor (incompatible combination) (Pattern A — 7 blinks)
  • P8 – Pipe temperature error (coil temperature not changing as expected) (Pattern A — 8 blinks. Check charge, sensor position, 4-way valve)
  • E4 – Remote controller signal receiving error (Pattern A — 9 blinks)
  • E5 – Remote controller signal receiving error
  • Fb – Indoor unit control system error (memory error etc.) (Pattern A — 12 blinks)
  • Pb – Indoor fan motor error
  • E0 – Remote controller transmission error
  • E3 – Remote controller transmission error
  • E1 – Remote controller control board error
  • E2 – Remote controller control board error
  • E9 – Indoor/outdoor communication error (outdoor transmitting error) (Pattern B — 1 blink)
  • UP – Compressor overcurrent interruption (Pattern B — 2 blinks)
  • U3 – Outdoor thermistor open/short (discharge TH4) (Pattern B — 3 blinks)
  • U4 – Outdoor thermistor open/short (TH3/TH6/TH7/TH8) (Pattern B — 3 blinks)
  • UF – Compressor overcurrent interruption (compressor locked) (Pattern B — 4 blinks)
  • U2 – Abnormal high discharge temperature / 49C activated / insufficient refrigerant (Pattern B — 5 blinks)
  • U1 – Abnormal high pressure (63H activated) (Pattern B — 6 blinks)
  • Ud – Overheat protection operation (Pattern B — 6 blinks)
  • U5 – Abnormal heatsink temperature (Pattern B — 7 blinks)
  • U8 – Outdoor fan protection stop (Pattern B — 8 blinks)
  • U6 – Compressor overcurrent interruption / power module abnormality (Pattern B — 9 blinks)
  • U7 – Abnormal superheat due to low discharge temperature (Pattern B — 10 blinks)
  • U9 – Abnormality such as over/under voltage or abnormal sync signal to main circuit (Pattern B — 11 blinks)
  • UH – Current sensor error (Pattern B — 11 blinks)
  • UL – Abnormal low pressure
  • PL – Refrigerant circuit abnormality

City Multi VRF / central controller 4-digit codes

Models: PUHY, PURY, PQHY, PEFY, PLFY, PKFY, PMFY, PCFY, AE-200, AG-150, CMB

How to read: 4-digit codes show on the central controller / ME remote and on the outdoor unit LED display.

  • 0403 – Serial communication error (outdoor PCB–inverter)
  • 1102 – Discharge temperature abnormality
  • 1301 – Low pressure abnormality
  • 1302 – High pressure abnormality
  • 1500 – Overcharged refrigerant
  • 2500 – Water leakage abnormality
  • 2502 – Drain pump abnormality
  • 2503 – Drain sensor / float switch abnormality
  • 4102 – Open phase
  • 4106 – Power supply abnormality (power failure)
  • 4115 – Power supply sync signal abnormality
  • 4220 – Inverter bus voltage abnormality
  • 4230 – Heatsink overheat protection
  • 4250 – Power module / overcurrent abnormality
  • 5101 – Return air / discharge thermistor abnormality
  • 5102 – Liquid pipe thermistor abnormality
  • 5103 – Gas pipe thermistor abnormality
  • 5201 – High pressure sensor abnormality
  • 6600 – Address duplication
  • 6602 – Transmission processor hardware error
  • 6603 – Transmission bus busy
  • 6606 – Communication error with transmission processor
  • 6607 – No ACK error
  • 6608 – No response error
  • 7100 – Total capacity error
  • 7101 – Capacity code error
  • 7102 – Connected unit count over
  • 7105 – Address setting error

MITSUBISHI HEAVY INDUSTRIES

Wall-mounted RAC split (SRK / SRF / SRR) — lamp codes

Models: SRK, SRF, SRR, SRC, SCM, Avanti, Bronte, Diamond

How to read: Indoor RUN and TIMER lamps flash to show the fault. Indoor faults: RUN lamp flashes with TIMER ON. Outdoor faults: TIMER lamp flashes with RUN ON, or RUN 'keeps flashing' with TIMER flashing N times. The equivalent E-code (shown on wired RC / service checker) is listed with each. In service mode the RUN lamp flashes the tens digit and TIMER the units digit (e.g. RUN 4 + TIMER 2 = stop code 42, current cut).

  • RUN×1 – Indoor heat exchanger sensor error (E6) (RUN 1 flash, TIMER ON)
  • RUN×2 – Room temperature sensor error (E7) (RUN 2 flashes, TIMER ON)
  • RUN×5 – Active filter voltage error (E47) (RUN 5 flashes)
  • RUN×6 – Indoor fan motor error (E16) (RUN 6 flashes — fan < 300 rpm for 30 s)
  • RUN×7 – Refrigeration cycle protective control (E57) — service valve closed / insufficient refrigerant (RUN 7 flashes)
  • TIMER×1 (RUN flashing) – Outdoor air temperature sensor error (E38) (RUN keeps flashing, TIMER 1)
  • TIMER×2 (RUN flashing) – Outdoor heat exchanger sensor error (E37) (RUN keeps flashing, TIMER 2)
  • TIMER×4 (RUN flashing) – Discharge pipe sensor error (E39) (RUN keeps flashing, TIMER 4)
  • TIMER×5 (RUN flashing) – Suction pipe sensor error (E53) (RUN keeps flashing, TIMER 5)
  • TIMER×6 (RUN flashing) – Power transistor overheat / sensor error (E41) (RUN keeps flashing, TIMER 6)
  • TIMER×1 – Current cut (E42) — compressor locked, open phase, shorted power transistor, closed valve (RUN ON, TIMER 1)
  • TIMER×2 – Trouble of outdoor unit (E59) — compressor wire broken / compressor blocked (RUN ON, TIMER 2)
  • TIMER×3 – Current safe stop (E58) — overload, overcharge, compressor locked (RUN ON, TIMER 3)
  • TIMER×4 – Power transistor error (E51) (RUN ON, TIMER 4)
  • TIMER×5 – Compressor overheat (E36) — gas shortage, discharge sensor, closed valve (RUN ON, TIMER 5)
  • TIMER×6 – Signal transmission error (E5) (RUN ON, TIMER 6)
  • TIMER×7 – Outdoor fan motor error (E48) (RUN ON, TIMER 7)
  • Cooling HP – Cooling high pressure protection (E35) (TIMER keeps flashing, RUN 2)
  • Rotor lock – Rotor lock — compressor magnetic pole position not detected (E60)

PAC / FDC commercial & ducted (wired RC-E5, RC-EX, RC-EXZ) — E codes

Models: FDC, FDT, FDU, FDUM, FDE, FDK, FDF, FDTC, SRR, RC-E5, RC-EX, RC-EXZ, KX

How to read: E-codes display on the wired remote controller. Indoor/outdoor PCB green/red LEDs also flash to confirm the fault location.

  • E1 – Remote controller communication error
  • E2 – Duplicate indoor unit address
  • E3 – Outdoor unit signal line error / CNK fuse
  • E5 – Indoor/outdoor transmission error (outdoor power off if on multiple units)
  • E6 – Indoor heat exchanger sensor (Thi-R) error
  • E7 – Return air sensor (Thi-A) error
  • E9 – Drain trouble (float switch activated)
  • E10 – Excessive number of units on one remote controller
  • E16 – Indoor fan motor error
  • E28 – Remote controller temperature sensor error
  • E35 – Cooling high pressure protection
  • E36 – Discharge temperature abnormality
  • E37 – Outdoor heat exchanger sensor (Tho-R) error
  • E38 – Outdoor air temperature sensor (Tho-A) error
  • E39 – Discharge pipe sensor (Tho-D) error
  • E40 – High pressure switch (63H1) / service valve closed
  • E41 – Power transistor overheat
  • E42 – Current cut
  • E45 – Communication error between inverter PCB and outdoor control PCB
  • E47 – Active filter / inverter voltage error
  • E48 – Outdoor fan motor error
  • E49 – Low pressure error
  • E51 – Inverter / power transistor abnormality
  • E53 – Suction pipe sensor error
  • E54 – Low pressure sensor error
  • E56 – Power transistor sensor disconnected / poor connection
  • E57 – Insufficient refrigerant
  • E58 – Current safe stop / anomalous compressor loss of synchronism
  • E59 – Compressor start-up failure
  • E60 – Compressor rotor position detection error

FUJITSU

Current split, ducted, cassette (lamp flashes & wired RC codes)

Models: ASTG, ASTH, ASTA, ASHH, ASYG, ASTB, ARTG, ARTH, ARTC, ARTA, AUTG, AUTH, AUTA, ABTG, AGTG, AGTV, AOTG, AOTH, AOTA, AOYG, AOHH, AJTA, AOTR, UTY-R, UTY-RN, UTY-RV, UTY-RS, Nocria, Lifestyle, Designer, Halcyon, General

How to read: Wireless units: count the OPERATION (green) and TIMER (orange) lamp flashes while the ECONOMY lamp flashes continuously. The two counts form the code (e.g. Operation 1 + Timer 1 = code 11). Wired controllers show the 2-digit code directly (press and hold the error/check button on UTY series). 'EE:EE' on older wired controllers: press Energy Save + Zone Control together >3 s to display the code. All three lamps flashing several times then switching off can be an accidentally-set Weekly Timer, not a fault.

  • 11 – Serial communication error (indoor–outdoor) (Operation 1 / Timer 1)
  • 12 – Wired remote controller communication error (Operation 1 / Timer 2)
  • 14 – Network communication error (Operation 1 / Timer 4)
  • 15 – Check run unfinished (Operation 1 / Timer 5)
  • 16 – Transmission / peripheral unit connection error (Operation 1 / Timer 6)
  • 21 – Refrigerant circuit address setting error (Operation 2 / Timer 1)
  • 22 – Indoor unit capacity error (Operation 2 / Timer 2)
  • 23 – Combination error (Operation 2 / Timer 3)
  • 24 – Connection unit number error (Operation 2 / Timer 4)
  • 26 – Address setting error (Operation 2 / Timer 6)
  • 27 – Master/slave unit set-up error (Operation 2 / Timer 7)
  • 29 – Connection unit number error in wired RC circuit (Operation 2 / Timer 9)
  • 31 – Power supply interruption error (Operation 3 / Timer 1)
  • 32 – Indoor PCB EEPROM error (Operation 3 / Timer 2)
  • 35 – Manual auto switch error (Operation 3 / Timer 5)
  • 3A – Indoor unit communication circuit (wired RC) error (Operation 3 / Timer 10)
  • 41 – Inlet (room) air temperature sensor error (Operation 4 / Timer 1)
  • 42 – Indoor heat exchanger middle temperature sensor error (Operation 4 / Timer 2)
  • 51 – Indoor unit fan motor error (Operation 5 / Timer 1)
  • 52 – Indoor EEV error (Operation 5 / Timer 2)
  • 53 – Drain pump error (Operation 5 / Timer 3)
  • 57 – Damper error (Operation 5 / Timer 7)
  • 58 – Intake grille error (Operation 5 / Timer 8)
  • 5U – Indoor unit error (Operation 5 / Timer 15)
  • 62 – Outdoor PCB / communication error (Operation 6 / Timer 2)
  • 63 – Inverter error (Operation 6 / Timer 3)
  • 64 – Active filter / PFC circuit error (Operation 6 / Timer 4)
  • 65 – Trip terminal 'L' error (Operation 6 / Timer 5)
  • 6A – Display PCB / communication error (Operation 6 / Timer 10)
  • 71 – Outdoor discharge temperature sensor error (Operation 7 / Timer 1)
  • 72 – Compressor temperature sensor error (Operation 7 / Timer 2)
  • 73 – Outdoor heat exchanger liquid temperature sensor error (Operation 7 / Timer 3)
  • 74 – Outdoor ambient temperature sensor error (Operation 7 / Timer 4)
  • 75 – Outdoor suction temperature sensor error (Operation 7 / Timer 5)
  • 76 – 2-way / 3-way valve temperature sensor error (Operation 7 / Timer 6)
  • 77 – Outdoor heatsink temperature sensor error (Operation 7 / Timer 7)
  • 82 – Sub-cool heat exchanger inlet/outlet sensor error (Operation 8 / Timer 2)
  • 83 – Outdoor liquid pipe temperature sensor error (Operation 8 / Timer 3)
  • 84 – Outdoor current sensor error (Operation 8 / Timer 4)
  • 86 – High/low pressure sensor or switch error (Operation 8 / Timer 6)
  • 94 – Outdoor current trip detection (Operation 9 / Timer 4)
  • 95 – Compressor rotor location detection error (Operation 9 / Timer 5)
  • 97 – Outdoor fan motor error (Operation 9 / Timer 7)
  • 98 – Outdoor fan motor 2 error (Operation 9 / Timer 8)
  • 99 – 4-way valve error (Operation 9 / Timer 9)
  • 9A – Coil (expansion valve) error (Operation 9 / Timer 10)
  • 9U – Outdoor unit error (Operation 9 / Timer 15)
  • A1 – Outdoor abnormal discharge temperature (Operation 10 / Timer 1)
  • A3 – Abnormal compressor temperature (Operation 10 / Timer 3)
  • A4 – High pressure error (Operation 10 / Timer 4)
  • A5 – Low pressure error (Operation 10 / Timer 5)
  • J1 – VRF branch box error (Operation 13 / Timer 1)
  • J2 – Multi branch box error (Operation 13 / Timer 2)

PANASONIC

Inverter split & ducted (CS / CU / S- / U- series)

Models: CS-, CU-, CS-Z, CS-RZ, CS-XZ, CS-XU, CS-NZ, CS-PU, CS-TZ, CS-MZ, CU-Z, CU-RZ, CU-XZ, CS-E, CU-E, S-, U-, CZ-RTC, Aero, Ecoi

How to read: Point the remote at the unit and press and hold CHECK (use a pin) for 5 s until '–' shows. Press TIMER/TEMP ▲▼ to step through codes; when the stored code is reached the indoor unit beeps continuously (and the power lamp lights). Press CHECK again to exit. Codes can also be read in the Panasonic Comfort Cloud app.

  • H00 – No memory of failure
  • H11 – Indoor/outdoor abnormal communication
  • H12 – Indoor unit capacity unmatched
  • H14 – Indoor intake air temperature sensor abnormality
  • H15 – Outdoor compressor temperature sensor abnormality
  • H16 – Outdoor current transformer (CT) abnormality
  • H17 – Outdoor suction temperature sensor abnormality
  • H19 – Indoor fan motor mechanism locked
  • H21 – Indoor float switch operation abnormality
  • H23 – Indoor heat exchanger temperature sensor 1 abnormality
  • H24 – Indoor heat exchanger temperature sensor 2 abnormality
  • H25 – Indoor ion device abnormality
  • H26 – Negative ion abnormality
  • H27 – Outdoor air temperature sensor abnormality
  • H28 – Outdoor heat exchanger temperature sensor 1 abnormality
  • H30 – Outdoor discharge pipe temperature sensor abnormality
  • H32 – Outdoor heat exchanger temperature sensor 2 abnormality
  • H33 – Indoor/outdoor wrong connection (mis-wiring / voltage)
  • H34 – Outdoor heatsink temperature sensor abnormality
  • H36 – Outdoor gas pipe temperature sensor abnormality
  • H37 – Outdoor liquid pipe temperature sensor abnormality
  • H38 – Indoor/outdoor mismatch (brand code)
  • H39 – Abnormal indoor operating or standby units (multi)
  • H41 – Abnormal wiring or piping connection (multi)
  • H50 – Ventilation fan motor locked
  • H51 – Ventilation fan motor locked
  • H52 – Left-right limit switch fixing abnormality
  • H58 – Indoor gas sensor abnormality
  • H59 – ECO sensor abnormality
  • H64 – Outdoor high pressure sensor abnormality
  • H67 – nanoe abnormality
  • H70 – Light sensor abnormality
  • H71 – DC cooling fan inside control board abnormality
  • H79 – Wireless LAN module write error
  • H85 – Indoor–wireless LAN module communication abnormality
  • H97 – Outdoor fan motor mechanism locked
  • H98 – Indoor high pressure protection (heating)
  • H99 – Indoor freeze protection (cooling)
  • F11 – 4-way valve switching abnormality
  • F16 – Total running current protection
  • F17 – Indoor standby units freezing abnormality (multi)
  • F18 – Dry circuit blocked
  • F87 – Control box overheating protection
  • F90 – PFC circuit protection / compressor microcomputer communication
  • F91 – Refrigeration cycle abnormality (low gas / blockage)
  • F93 – Compressor abnormal revolution
  • F94 – Compressor discharge pressure overshoot protection
  • F95 – Outdoor cooling high pressure protection
  • F96 – Power transistor (IPM) module overheating protection
  • F97 – Compressor overheating protection
  • F98 – Total running current protection
  • F99 – Outdoor DC peak detection

SAMSUNG

Residential & light commercial split (Wind-Free, AR series, ducted, cassette)

Models: AR, AJ, AC, AM, AE, WindFree, Wind-Free, AR09, AR12, AR18, AR24, AC071, AC100, AC140, MWR-, MWR-WE

How to read: Codes display on the indoor unit (blinking digits) or wired controller. Some displays show an abbreviated form (e.g. C1 21 / 'E1 21' for E121) depending on the model. Outdoor PCB LEDs/7-segment also show the code.

  • E101 – Communication error indoor–outdoor (no communication for 1 min)
  • E102 – Communication error indoor–outdoor (after tracking)
  • E108 – Duplicate communication address
  • E121 – Indoor room temperature sensor error (open/short)
  • E122 – Indoor heat exchanger (EVA in) sensor error
  • E123 – Indoor heat exchanger (EVA out) sensor error
  • E128 – Indoor EVA in sensor detached
  • E129 – Indoor EVA out sensor detached
  • E151 – Indoor EEV open error
  • E153 – Float switch activated (drain)
  • E154 – Indoor fan error
  • E162 – Indoor EEPROM error
  • E163 – Indoor EEPROM option error
  • E186 – Indoor MPI / Wi-Fi module communication error
  • E201 – Communication error — number of indoor units mismatch / after tracking
  • E202 – Communication timeout (indoor–outdoor)
  • E203 – Communication timeout between inverter micom and main micom
  • E221 – Outdoor temperature sensor error
  • E231 – Condenser (COND) temperature sensor error
  • E251 – Discharge temperature sensor error
  • E320 – OLP (compressor top) temperature sensor error
  • E403 – Freeze protection (cooling)
  • E404 – Overload protection (heating)
  • E416 – Discharge temperature too high
  • E422 – Outdoor EEV blocked / closed self-diagnosis error
  • E425 – Phase reversal / missing phase
  • E440 – Heating operation prohibited (outdoor temperature)
  • E441 – Cooling operation prohibited (outdoor temperature)
  • E458 – Outdoor fan error
  • E461 – Compressor start failure
  • E462 – Total current / PFC overcurrent error
  • E463 – OLP (compressor top) overheat
  • E464 – IPM overcurrent
  • E465 – Compressor overload error
  • E466 – DC link over/under voltage
  • E467 – Compressor rotation error / compressor wire missing
  • E468 – Current sensor error
  • E469 – DC link voltage sensor error
  • E470 – Outdoor EEPROM error
  • E471 – Outdoor EEPROM OTP error
  • E474 – IPM / heatsink temperature sensor error
  • E483 – Hardware DC link overvoltage
  • E484 – PFC overload
  • E485 – Input current sensor error
  • E488 – AC input voltage sensor error
  • E500 – Heatsink over-temperature
  • E554 – Gas leak detected (refrigerant shortage)

DVM S VRF & CAC commercial (ducted, cassette, ERV) — additional codes

Models: AM, AM080, AM100, AM120, AM160, AM200, DVM, DVM S, DVM S2, DVM Eco, CAC, ERV, MIM-, MWR-WE13, MWR-WW

How to read: Codes show on the wired controller and outdoor 7-segment display. DVM shows E for codes 101–700. Some indoor display panels split the code (e.g. 'E1' then '21'). All residential codes in the Samsung split series also apply; these are additional DVM/CAC codes.

  • E108 – Duplicate communication address
  • E131 – Indoor heater sensor error
  • E151 – Indoor EEV open failure
  • E152 – Indoor EEV close failure
  • E323 – Suction sensor 2 error (open/short)
  • E346 – Outdoor fan 2 operation failure
  • E347 – Outdoor fan 2 motor wire not connected
  • E348 – Outdoor fan 2 lock
  • E407 – Compressor down — high pressure protection control
  • E410 – Compressor down — low pressure protection control
  • E428 – Start suspended — abnormal compression ratio
  • E455 – Outdoor fan 1 IPM overheat

LG

Split, ducted, cassette & multi (Dual Inverter, ARTCOOL, Multi V S)

Models: S3, S4, WH, WS, H09, H12, H18, H24, B18, B24, AMNW, ABNW, CT, UU, UL, ZBNW, PREMTB, ArtCool, ARTCOOL, Dual Inverter, Multi V

How to read: Codes show on the indoor display or wired controller as CH## (shown as e.g. 'CH' then '05' alternately). On some displays the format is C# / E# / F#. Without a display, the indoor LED blinks the code (e.g. 5 blinks = CH05). Outdoor PCB LEDs blink 2-digit codes (tens then units).

  • CH01 – Indoor room air (intake) sensor open/short
  • CH02 – Indoor pipe (inlet) sensor open/short
  • CH03 – Wired remote controller communication error
  • CH04 – Drain pump / float switch error
  • CH05 – Indoor–outdoor communication error
  • CH06 – Indoor pipe (outlet) sensor open/short
  • CH07 – Different operating modes selected (multi)
  • CH09 – Indoor EEPROM error
  • CH10 – Indoor BLDC fan motor lock
  • CH21 – DC peak / IPM fault (compressor overcurrent)
  • CH22 – Input current over (CT2 max current)
  • CH23 – DC link low voltage
  • CH24 – High pressure switch / pressure abnormality
  • CH25 – AC input voltage abnormal (over/under)
  • CH26 – DC compressor position / start error
  • CH27 – PFC fault (AC input instant overcurrent)
  • CH29 – Compressor phase overcurrent
  • CH32 – Inverter compressor discharge temperature high
  • CH34 – High pressure protection
  • CH35 – Low pressure protection
  • CH38 – Low refrigerant protection
  • CH40 – Current transformer (CT) sensor error
  • CH41 – Discharge pipe sensor open/short
  • CH44 – Outdoor air sensor open/short
  • CH45 – Outdoor coil (condenser middle) sensor open/short
  • CH46 – Suction pipe sensor open/short
  • CH48 – Condenser outlet pipe sensor open/short
  • CH51 – Over-capacity — indoor units exceed outdoor capacity
  • CH53 – Communication error (detected by outdoor unit)
  • CH54 – Open phase / reverse phase (3 phase)
  • CH60 – Outdoor EEPROM error
  • CH61 – Condenser pipe high temperature (outdoor overheat in cooling / indoor in heating)
  • CH62 – Heatsink high temperature
  • CH65 – Heatsink sensor open/short (On Multi V the manual also lists outdoor liquid pipe sensor — check both)
  • CH67 – Outdoor BLDC fan motor lock
  • CH73 – Input instant overcurrent (peak)

TOSHIBA

Commercial & ducted RAV (wired RB-RBC) — check codes

Models: RAV-, RAV-GM, RAV-RM, RAV-SM, RAV-SP, RAV-GP, RBC-, Digital Inverter, Super Digital Inverter

How to read: Check codes show on the wired controller (RBC-AMS/ASCU). Press the CHECK/TEST (or hold ON/OFF + ▼) to view history. Outdoor 7-segment display shows the same code family. Wireless sensor units flash Operation/Timer/Ready lamps — see service manual table.

  • E01 – No header remote controller / remote communication error
  • E02 – Remote controller send error
  • E03 – Indoor–remote periodic communication error
  • E04 – Indoor–outdoor serial communication error
  • E08 – Duplicated indoor address
  • E09 – Duplicated header remote controller
  • E10 – Communication error between indoor MCUs
  • E18 – Header–follower indoor communication error
  • F01 – Indoor heat exchanger sensor (TCJ) error
  • F02 – Indoor heat exchanger sensor (TC) error
  • F04 – Outdoor discharge sensor (TD) error
  • F06 – Outdoor heat exchanger sensor (TE/TS) error
  • F07 – Outdoor TL sensor error
  • F08 – Outdoor air sensor (TO) error
  • F10 – Indoor room sensor (TA) error
  • F12 – Suction sensor (TS) error
  • F13 – Heatsink sensor (TH) error
  • F15 – Outdoor temperature sensor misplaced/miswired (TE/TS)
  • F29 – Indoor EEPROM / other indoor PCB error
  • F31 – Outdoor EEPROM error
  • H01 – Compressor breakdown
  • H02 – Compressor lock
  • H03 – Current detection circuit error
  • H04 – Case thermostat operation
  • L03 – Duplicated header indoor units (group)
  • L07 – Group line connected to individual indoor unit
  • L08 – Indoor group address not set
  • L09 – Indoor capacity not set
  • L10 – Outdoor capacity not set (service PCB)
  • L29 – Other outdoor unit error
  • L30 – External interlock / abnormal stop input
  • P01 – Indoor fan motor error (AC fan)
  • P03 – Discharge temperature error
  • P04 – High pressure switch operated
  • P05 – Power supply error / open phase
  • P07 – Heatsink overheat
  • P10 – Indoor water overflow (drain)
  • P12 – Indoor DC fan motor error
  • P15 – Gas leak detection
  • P19 – 4-way valve error
  • P20 – High pressure protection
  • P22 – Outdoor fan error
  • P26 – Inverter G-Tr (IGBT) short protection
  • P29 – Compressor position detection circuit error
  • P31 – Other indoor unit error (group follower)

Wall-mounted RAS split — 2-digit self-diagnosis codes

Models: RAS-, RAS-B, RAS-M, RAS-N, RAS-G, RAS-J, RAS-E2, Seiya, Shorai, Daiseikai, Haori, 42NQV, NQV

How to read: Point the remote at the unit and press CHECK (pin) — '00' shows. Press TIMER ▲ repeatedly; the unit beeps (and lamps flash) when the stored code is reached. Press CHECK to exit.

  • 00 – Normal
  • 04 – Return serial signal not received — interconnect wiring, compressor thermo, gas shortage; check 25A/3.15A inverter fuses
  • 05 – Indoor–outdoor operation signal error
  • 07 – Return serial signal stopped mid-operation — compressor thermo operated, gas shortage/leak or momentary power failure
  • 08 – 4-way valve switching error
  • 09 – Other refrigeration cycle error
  • 0B – Indoor water overflow detected
  • 0C – Room temperature sensor (TA) error
  • 0D – Indoor heat exchanger sensor (TC) error
  • 0F – Indoor heat exchanger sensor (TCJ) error
  • 11 – Indoor fan motor error
  • 12 – Other indoor PCB error
  • 14 – Inverter IGBT / G-Tr short circuit
  • 16 – Compressor position detection error
  • 17 – Current detection circuit error
  • 18 – Outdoor heat exchanger (TE) or suction (TS) sensor error
  • 19 – Discharge temperature sensor (TD) error
  • 1A – Outdoor fan motor error
  • 1B – Outdoor air temperature sensor (TO) error
  • 1C – Compressor drive output error (lock, missing phase) / indoor–outdoor miswiring — check PMV (Check interconnect wiring order first)
  • 1D – Compressor lock (not rotating)
  • 1E – Discharge temperature exceeded 117 °C — check TD sensor, gas leak, PMV
  • 1F – Compressor breakdown
  • 21 – High pressure switch operated

SMMS / MiNi-SMMS VRF — system check codes

Models: MMY-, MCY-, MMD-, MMU-, MMK-, MMF-, SMMS, SMMS-e, SMMS-i, SMMS-u, MiNi-SMMS

How to read: Codes show on the indoor wired remote and on the outdoor 7-segment display (set SW01=1, SW02=1, SW03=1). The 7-segment alternates the check code (3 s) with an auxiliary code (1 s) — e.g. compressor number, unit address or sensor number. The RAV check codes (E01–E04, F-, H01–H03, P-) also apply to indoor units on these systems.

  • E06 – Decrease in number of indoor units (indoor unit that was communicating stopped responding) (Aux: number of indoor units received normally)
  • E07 – Indoor/outdoor communication circuit error (outdoor cannot transmit to indoor units)
  • E08 – Duplicated indoor unit addresses
  • E12 – Automatic addressing start error (Aux 01: indoor–outdoor; 02: outdoor–outdoor)
  • E15 – No indoor unit found during automatic addressing
  • E16 – Indoor capacity over (>135% of outdoor) / too many units connected (Aux 00: capacity over; 01+: number connected)
  • E19 – Header outdoor unit quantity error (Aux 00: no header; 02: two or more headers)
  • E20 – Other refrigerant line connected during automatic addressing
  • E31 – IPDU (inverter board) communication error (Aux: IPDU quantity information)
  • F23 – Low pressure sensor (Ps) error — output voltage zero
  • H05 – Discharge sensor TD1 miswiring / not attached
  • H06 – Low pressure protective operation
  • H07 – Oil level down detection protection
  • H08 – Oil level detection sensor (TK) trouble (Aux 01–04: TK1–TK4)
  • H16 – Oil level detection circuit trouble
  • H25 – Discharge sensor TD3 miswiring
  • P20 – High pressure protective operation

ACTRONAIR

Serene, Aurora, Cascade wall/cassette & Ultra Slim ducted (R-410A, legacy codes)

Models: WRC, WRE, SWB, URC, CRE, LRE, Serene, Aurora, Cascade, Ultra Slim, Ultraslim

How to read: Code shows on the indoor display. Units without a display flash the Operation lamp (indoor faults, Timer OFF) or Operation lamp with Timer ON (outdoor sensor faults) — count the flashes. Timer-lamp-only flashes indicate P-codes (outdoor protection).

  • E0 – Indoor EEPROM parameter error (Operation lamp 1 flash)
  • E1 – Indoor–outdoor communication error (Operation lamp 2 flashes)
  • E2 – Zero-crossing signal detection error (Operation lamp 3 flashes)
  • E3 – Indoor fan speed out of control (Operation lamp 4 flashes)
  • E4 – Indoor room temperature sensor (T1) open/short (Operation lamp 5 flashes)
  • E5 – Evaporator coil sensor (T2) open/short (Operation lamp 6 flashes)
  • E7 – Indoor PCB–display board communication error
  • EC – Refrigerant leak detected (T2 not dropping in cooling) (Operation lamp 7 flashes)
  • EE – Water-level alarm (cassette/ducted) (Operation lamp 8 flashes)
  • F0 – Overload current protection (Operation 1 flash, Timer ON)
  • F1 – Outdoor ambient sensor (T4) open/short (Operation 2, Timer ON)
  • F2 – Condenser coil sensor (T3) open/short (Operation 3, Timer ON)
  • F3 – Discharge temperature sensor (T5) open/short (Operation 4, Timer ON)
  • F4 – Outdoor EEPROM parameter error (Operation 5, Timer ON)
  • F5 – Outdoor fan speed out of control (Operation 6, Timer ON)
  • F6 – Evaporator outlet sensor (T2B) open/short (Operation 7, Timer ON)
  • P0 – IPM malfunction or IGBT overcurrent protection (Timer lamp 1 flash)
  • P1 – Over-voltage or under-voltage protection (Timer lamp 2 flashes)
  • P2 – Compressor top / IPM high temperature protection (Timer lamp 3 flashes)
  • P3 – Low outdoor ambient temperature protection (Timer lamp 4 flashes)
  • P4 – Inverter compressor drive error (Timer lamp 5 flashes)
  • P6 – Compressor voltage protection / high-low pressure (Timer lamp 7 flashes)
  • CP – Remote on/off terminal open circuit
  • E8 – Master–slave communication error (twin) (Operation 9 flashes)
  • E9 – Other indoor unit malfunction (twin) (Operation 10 flashes)
  • P7 – Outdoor IGBT temperature sensor faulty (Timer 8 flashes)
  • J0 – Evaporator high temperature protection
  • J1 – Condenser high temperature protection
  • J2 – High discharge temperature protection
  • J3 – PFC module protection
  • J4 – Communication error outdoor main chip–compressor drive chip
  • J5 – High pressure protection
  • J6 – Low pressure protection
  • J8 – AC input voltage protection

Cascade R-32 & Ultra Slim 2 R-32 (URC/CRC/LRC)

Models: CRC, LRC, URC, Ultra Slim 2, Cascade R32

How to read: Newer R-32 units show 4-character codes (EH/EL/EC/PC). Many display briefly as 2 characters then 2 more, or show via the remote: press LED/Display 4 times (or 'Self Clean'/'Turbo' combinations on some remotes) to show the full code. The legacy 2-character equivalents are shown on older models.

  • EH00 – Indoor EEPROM parameter error (Operation 1 flash)
  • EH0A – Indoor EEPROM parameter error
  • EL01 – Indoor–outdoor communication error (Operation 2 flashes)
  • EH02 – Zero-crossing signal detection error
  • EH03 – Indoor fan speed outside normal range (Operation 4 flashes)
  • EH60 – Indoor room temperature sensor (T1) open/short (Operation 6 flashes)
  • EH61 – Evaporator coil sensor (T2) open/short (Operation 6 flashes)
  • EL0C – Refrigerant leak detection (Operation 8 flashes)
  • EH0b – Communication error between indoor main board and display (Operation 9 flashes)
  • EH0E – Water-level alarm (Operation 13 flashes)
  • EC51 – Outdoor EEPROM parameter error
  • EC52 – Condenser coil sensor (T3) open/short
  • EC53 – Outdoor ambient sensor (T4) open/short
  • EC54 – Discharge sensor (TP) open/short
  • EC56 – Evaporator outlet sensor (T2B) open/short (multi)
  • EC07 – Outdoor fan speed outside normal range
  • EC0d – Outdoor unit malfunction
  • PC00 – IPM malfunction or IGBT overcurrent protection
  • PC01 – Over-voltage or under-voltage protection
  • PC02 – Compressor top / IPM high temperature protection
  • PC03 – High or low pressure protection
  • PC04 – Inverter compressor drive error
  • PC08 – Outdoor current overload protection
  • PC40 – Communication error between outdoor main chip and compressor driven chip
  • LC06 – Low ambient / anti-cold protection

Classic split ducted (SRE/SRA/SRG) & ESP Digital (SRD/SRV) — LM7/LM24 controllers

Models: SRE, SRA, SRG, SRD, SRV, LM7, LM24, ESP Digital, Classic, ESP Plus, ESP Ultima

How to read: Fault shows on the LM7/LM24 wall controller as E#, and as a digit on the outdoor CPU display. 24-hr controllers may flash a single digit or the Heat & Cool indicators together.

  • E2 – Indoor coil-out sensor fault (open/short) (ESP Digital)
  • E3 – Room sensor fault (open/short)
  • E4 – Indoor coil-in sensor fault (open/short)
  • E5 – Indoor–outdoor communication error
  • E6 – Discharge high temperature (likely low refrigerant) (Outdoor CPU '6')
  • E7 – Outdoor coil sensor fault (open/short) (Outdoor CPU '7')
  • E8 – Outdoor discharge sensor fault (Outdoor CPU '8')
  • E9 – High or low pressure / phase error (Outdoor CPU '9')
  • 0 – Cooling mode (Outdoor CPU)
  • 1 – Heating mode (Outdoor CPU)
  • 2 – Heating — compressor run over 20 min (Outdoor CPU)
  • 3 – Heating — defrost (Outdoor CPU)
  • 4 – Overheat or anti-freeze protection (low capacity) (Outdoor CPU)
  • 5 – Heating — indoor coil pre-heat after defrost (Outdoor CPU; Heat blink every 8 s)

Classic 2, Advance, Aires & Variable Commercial (NEO / LR7 / LC7 controllers, 2-digit E codes)

Models: CRA, CCA, EVA, EAA, EFA, CRV, EVV, EFV, CRS, PRV, PKV, NEO, LR7, LC7, Advance, Aires, Classic 2

How to read: Fault shows on the NEO / LR7-1 / LC7-2 controller and the outdoor 7-segment display. Some faults (E09/E11) only show on the wall controller after several occurrences — check the outdoor display/history.

  • E01 – Indoor fan RPM feedback error
  • E02 – Indoor coil sensor error
  • E03 – Indoor room temperature sensor error
  • E04 – Indoor coil-in temperature sensor error
  • E06 – High discharge temperature (>120 °C Advance / >138 °C Aires)
  • E07 – Outdoor coil temperature sensor error
  • E08 – Discharge temperature sensor error
  • E09 – LP switch tripped (or phase sequence relay)
  • E10 – LP sensor error
  • E11 – HP switch tripped
  • E12 – HP sensor error
  • E13 – Other drive errors (check VSD)
  • E15 – ODU–VSD communication error
  • E18 – Suction temperature sensor error
  • E22 – Ambient temperature sensor error
  • E26 – VSD supply over-current
  • E27 – VSD supply over-voltage
  • E28 – VSD temperature high
  • E29 – VSD low supply voltage
  • E30 – VSD trip lock
  • E41 – VSD DC link voltage low
  • E42 – Envelope protection — extreme low evaporating pressure
  • E43 – Envelope protection — high compression ratio
  • E44 – Envelope protection — high condensing pressure
  • E45 – Envelope protection — low compression ratio
  • E47 – Compressor torque limit error
  • E50 – Outdoor board configuration error
  • E51 – Indoor–outdoor unit communication error
  • E52 – Indoor unit–wall controller communication error
  • E53 – Indoor–master control communication error
  • E54 – No Modbus packets from indoor fan (30 s)
  • E55 – BMS–ODU communication error
  • E56 – No master wall controller detected
  • E60 – VSD compressor phase over-current
  • E61 – VSD compressor loss of phase
  • E62 – VSD DC bus over-voltage
  • E63 – VSD DC bus under-voltage
  • E64 – VSD compressor loss of rotor
  • E66 – AC voltage imbalance / input loss of phase
  • E67 – Inverter de-saturation
  • E69 – VSD PFC-IGBT over-temperature
  • E70 – VSD lost rotor position
  • E71 – VSD motor temperature sensor error
  • E72 – VSD pre-charge relay open
  • E74 – VSD IGBT over-current / choke wiring
  • E79 – IPM desat / compressor hardware over-current
  • E80 – Motor temperature high
  • E81 – Drive board temperature high
  • E82 – Power module temperature high
  • E84 – DSP–PFC communication error
  • E85 – Comms–DSP communication error
  • E86 – Compressor phase current imbalance
  • E88 – Micro electronics / drive EEPROM error
  • E89 – Motor over-speed
  • E90 – Compressor model configuration error
  • E99 – Compressor overload / other malfunction
  • E104 – Fault limit lockout
  • dEF – Defrost
  • oiLr – Oil return operation
  • dr-1 – Demand response mode 1 (dr-2, dr-3 similar)
  • ohP – Derating — overheat protection
  • dtP – Derating — discharge temperature protection
  • cPP – Derating — condenser pressure protection
  • hSP – Derating — high suction pressure protection

ESP Platinum & ESP QUE Platinum (LM7/LM24/LM-ZC, QUE controllers)

Models: CRV, ERV, ARV, FRV, ERM, CRQ, ERQ, FRQ, QUE, Que, LM-ZC, ESP Platinum, Platinum

How to read: Fault shows on the wall controller (QUE: Tech Menu → fault history) and the outdoor 7-segment display. 'boot' shows for 30 s at power-up. Faults may not appear on the wall controller until they occur several times.

  • E3 – Room sensor error
  • E4 – Indoor coil inlet sensor error
  • E5 – Indoor–outdoor communication error
  • E6 – High discharge temperature (>138 °C)
  • E7 – Outdoor coil sensor error
  • E8 – Outdoor discharge sensor error
  • E9 – LP tripped
  • E10 – LP sensor error
  • E11 – HP tripped
  • E12 – HP sensor error
  • E14 – Condenser pressure low
  • E15 – VSD communication error
  • E17 – Peripherals error
  • E18 – EEV module suction temperature sensor open
  • E19 – EEV module suction temperature sensor short
  • E22 – Ambient sensor failure (safe mode)
  • E23 – EEV board communication failure (safe mode)
  • E25 – Ambient temperature not updated
  • E26 – VSD over-current
  • E27 – VSD over-voltage
  • E28 – VSD temperature high
  • E29 – VSD low supply voltage
  • E30 – VSD trip lock
  • E31 – VSD internal error
  • E32 – Envelope protection (HP/LP via VSD pressure sensors)
  • E33 – Envelope protection (HP/LP via VSD pressure sensors)
  • E34 – Derating — high VSD temperature
  • E35 – Derating — low suction pressure
  • E36 – Derating — low condenser pressure
  • E37 – Derating — high condenser pressure (also coil pre-heat after defrost)
  • E38 – Derating — output power limit
  • E39 – Defrost timed out
  • E40 – VSD restarting too frequently
  • E41 – VSD DC link voltage low

Commercial split (SCA/SCG) & package (PCA/PCG) — C7 controller

Models: SCA, SCG, PCA, PCG, C7

How to read: Fault shows on the C7 wall controller and outdoor CPU display.

  • E5 – Outdoor–indoor communication error
  • E7 – Outdoor coil sensor open/short circuit (Outdoor CPU 7 = open, 8 = short)
  • E9 – High–low pressure fault (Outdoor CPU 9)

CARRIER

QHC, 38QHF, QHF Aspire & ductless (Midea-built) — 2-character codes

Models: QHC, 42QHC, 38QHC, 38QHF, QHF, Aspire, 2-38QHF092, 40MAQ, 38MAQ, 40MBF, 40MBD, 40MBQ, 40MBC, 40QSM, 38QUA, 40QUA, 38MPRAQ, 42Q, 38Q, 42QHC, 42QHB, 38QHC, 40VC, 40MBAB, 40GVM, 38GVM, Carrier

How to read: Code shows on the indoor display. Units without a display flash the Operation lamp (indoor faults, Timer OFF) or Operation lamp with Timer ON (outdoor sensor faults) — count the flashes. Timer-lamp-only flashes indicate P-codes (outdoor protection). Carrier ductless units share the Midea control platform, so codes match the Midea family. On the QHF Aspire sheet, F0 (current overload) is listed as 'E0 with timer lamp on'.

  • E0 – Indoor EEPROM parameter error (Operation lamp 1 flash)
  • E1 – Indoor–outdoor communication error (Operation lamp 2 flashes · TCS field note: check indoor and outdoor boards)
  • E2 – Zero-crossing signal detection error (Operation lamp 3 flashes)
  • E3 – Indoor fan speed out of control (Operation lamp 4 flashes · TCS field note: indoor board and fan motor)
  • E4 – Indoor room temperature sensor (T1) open/short (Operation lamp 5 flashes)
  • E5 – Evaporator coil sensor (T2) open/short (Operation lamp 6 flashes)
  • E7 – Indoor PCB–display board communication error
  • EC – Refrigerant leak detected (T2 not dropping in cooling) (Operation lamp 7 flashes · TCS field note: unit has no refrigerant)
  • EE – Water-level alarm (cassette/ducted) (Operation lamp 8 flashes)
  • F0 – Overload current protection (Operation 1 flash, Timer ON)
  • F1 – Outdoor ambient sensor (T4) open/short (Operation 2, Timer ON)
  • F2 – Condenser coil sensor (T3) open/short (Operation 3, Timer ON)
  • F3 – Discharge temperature sensor (T5) open/short (Operation 4, Timer ON)
  • F4 – Outdoor EEPROM parameter error (Operation 5, Timer ON · TCS field note: outdoor main and inverter board)
  • F5 – Outdoor fan speed out of control (Operation 6, Timer ON)
  • F6 – Evaporator outlet sensor (T2B) open/short (Operation 7, Timer ON)
  • P0 – IPM malfunction or IGBT overcurrent protection (Timer lamp 1 flash · TCS field note: inverter board)
  • P1 – Over-voltage or under-voltage protection (Timer lamp 2 flashes)
  • P2 – Compressor top / IPM high temperature protection (Timer lamp 3 flashes)
  • P3 – Low outdoor ambient temperature protection (Timer lamp 4 flashes)
  • P4 – Inverter compressor drive error (Timer lamp 5 flashes · TCS field note: inverter board or compressor)
  • P6 – Compressor voltage protection / high-low pressure (Timer lamp 7 flashes)
  • CP – Remote on/off terminal open circuit
  • F8 – Lifting panel malfunction (40MBF floor/ceiling) (Operation 9 flashes, Timer ON)
  • F9 – Lifting panel not closed (40MBF) (Operation 10 flashes, Timer ON)

Elite inverter splits (42LUVH…N, …N-1, …K / 38LUVH)

Models: 42LUVH, 38LUVH, 42-38LUVH, LUVH, Elite, 42LUVH025N, 42LUVH035N, 42LUVH045N, 42LUVH055N, 42LUVH065N, 42LUVH075N, 42LUVH060K, 42LUVH070K, 42LUVH080K

How to read: Code shows on the indoor display. Models without a display (e.g. 42LUVH075N, 42LUVH080K) flash the Defrost/Timer/Auto/Operation lamps instead — see the Carrier sheet for the lamp pattern. E4 and P3 are reserved (not used). NOTE: E5, E6, E7 and P2 mean different things here than on QHC/Midea units.

  • E0 – EEPROM parameter error (Indoor PCB — replace if persistent)
  • E1 – Indoor/outdoor communication protection (TCS field note: check indoor and outdoor boards)
  • E2 – Zero-crossing signal error
  • E3 – Indoor fan speed out of control (TCS field note: indoor board and fan motor)
  • E5 – Outdoor temperature sensor open/short (on -1 models: or outdoor EEPROM error)
  • E6 – Room or evaporator temperature sensor open/short
  • E7 – Outdoor fan protection / outdoor fan speed out of control
  • P0 – IPM module protection / IGBT over-current (TCS field note: inverter board)
  • P1 – Over-voltage or under-voltage protection
  • P2 – Compressor top temperature protection
  • P4 – Inverter compressor drive error (TCS field note: inverter board or compressor)

TSV cassette & SHV inverter ducted indoor units — display codes

Models: TSV, SHV, SHV Inverter Ducted, TSV Cassette, SHDV, SHDS

How to read: Indoor codes show on the digital display or as Running/Timer/Defrost/Alarm lamp flashes. Outdoor codes show on the outdoor PCB 2-digit display — see the TSV/SHV outdoor series.

  • E1 – Indoor/outdoor communication malfunction (Timer lamp flashes)
  • E2 – Room temperature sensor (T1) open/short (Running lamp flashes)
  • E3 – Indoor coil middle sensor (T2) open/short (Running lamp flashes)
  • E4 – Indoor coil outlet sensor (T2B) open/short (Running lamp flashes)
  • EE – Water-level alarm (drain) (Alarm lamp flashes)
  • E7 – Indoor EEPROM malfunction (Running lamp slow flash)
  • Ed – Outdoor unit malfunction — read outdoor display (Alarm lamp slow flash)
  • E8 – Indoor fan speed out of control (Running & Timer lamps flash)
  • F0 – Communication error between main PCB and up-down panel PCB
  • F1 – Up-down (lifting) panel malfunction
  • F3 – Master/slave unit communication malfunction (twin)
  • F4 – Other malfunction of master or slave unit (twin)

TSV cassette & SHV inverter ducted outdoor units — PCB display codes

Models: TSV, SHV, SHV Inverter Ducted, TSV Cassette

How to read: Read on the 2-digit display on the outdoor main PCB. T1 room, T2 coil middle, T2B coil outlet, T3 condenser coil, T4 outdoor ambient, T5 discharge.

  • E0 – Outdoor EEPROM malfunction
  • E2 – Indoor/outdoor communication error
  • E3 – Communication error between IPM board and outdoor main board
  • E4 – Outdoor T3 or T4 temperature sensor open/short
  • E5 – Compressor voltage protection
  • E6 – PFC module protection (models with PFC board)
  • E8 – Outdoor fan speed out of control
  • P0 – Compressor top temperature protection
  • P1 – High pressure protection (model specific)
  • P2 – Low pressure protection (model specific)
  • P3 – Compressor current protection
  • P4 – Compressor discharge temperature protection
  • P5 – Condenser high temperature protection
  • P6 – IPM module protection
  • P7 – Evaporator high temperature protection

42NQV & 42CMD multi (Toshiba-built) — 2-digit check codes

Models: 42NQV, NQV, 42NQV025, 42NQV035, 42NQV045, 42NQV050, 42NQV060, 42CMD, 38CMS, Carrier Multi

How to read: Point the remote at the unit and press CHECK (pin) — '00' shows. Press TIMER ▲ repeatedly; the unit beeps (and lamps flash) when the stored code is reached. Press CHECK to exit. Indoor lamp block: 00 = indoor PCB (Operation 5 Hz), 01 = connecting cable/serial signal (Operation+Timer), 02 = outdoor PCB (Operation+Filter), 03 = others incl. compressor (all three). Press CLR in check mode to clear stored codes ('7F').

  • 00 – Normal
  • 04 – Return serial signal not received — interconnect wiring, compressor thermo, gas shortage; check 25A/3.15A inverter fuses
  • 05 – Indoor–outdoor operation signal error
  • 07 – Return serial signal stopped mid-operation — compressor thermo operated, gas shortage/leak or momentary power failure
  • 08 – 4-way valve switching error
  • 09 – Other refrigeration cycle error
  • 0B – Indoor water overflow detected
  • 0C – Room temperature sensor (TA) error
  • 0D – Indoor heat exchanger sensor (TC) error
  • 0F – Indoor heat exchanger sensor (TCJ) error
  • 11 – Indoor fan motor error
  • 12 – Other indoor PCB error
  • 14 – Inverter IGBT / G-Tr short circuit
  • 16 – Compressor position detection error
  • 17 – Current detection circuit error
  • 18 – Outdoor heat exchanger (TE) or suction (TS) sensor error
  • 19 – Discharge temperature sensor (TD) error
  • 1A – Outdoor fan motor error
  • 1B – Outdoor air temperature sensor (TO) error
  • 1C – Compressor drive output error (lock, missing phase) / indoor–outdoor miswiring — check PMV (Check interconnect wiring order first)
  • 1D – Compressor lock (not rotating)
  • 1E – Discharge temperature exceeded 117 °C — check TD sensor, gas leak, PMV
  • 1F – Compressor breakdown
  • 21 – High pressure switch operated

VYX Xpower outdoor (38VYX080/110/130) — cycle PCB LED codes

Models: VYX080, VYX110, VYX130, Xpower

How to read: Set SW800 bits 1–4 OFF on the outdoor cycle control PCB and read LEDs D800–D803; the code number is shown below. Indoor units show Toshiba RAV-style check codes (E04, F04, P03…) on the wired remote — search the Toshiba RAV series. VYX050 is diagnosed from the indoor unit only.

  • 1 – Heat exchanger sensor (TE) error
  • 2 – Suction sensor (TS) error
  • 3 – Hot gas discharge sensor (TD) error
  • 4 – High pressure protection error
  • 5 – Outdoor air temperature sensor (TO) error
  • 6 – Outdoor DC fan motor error
  • 7 – Communication error between IPDU (abnormal stop)
  • 8 – High pressure release operation
  • 9 – Discharge temperature error — hot gas too high
  • 10 – EEPROM error
  • 11 – Communication error between IPDU (no abnormal stop)
  • 12 – G-Tr short-circuit protection
  • 13 – Detect circuit error
  • 14 – Current sensor error
  • 15 – Compressor lock error
  • 16 – Compressor breakdown

38VYX030/040, P series & G series (LG-built) — indoor green LED rank codes

Models: 38VYX030, 38VYX040, P series, G series, Carrier P, Carrier G

How to read: The indoor green LED flashes a pattern, pauses 3 s, repeats. Codes are the number of flashes (e.g. 7 = seven flashes). If more than one error occurs the highest-rank one shows first. Units run in FAN ONLY mode for most of these faults.

  • 9 – Power line feedback (zero-crossing) error (Rank 1)
  • 7 – Indoor/outdoor communication fault (Rank 2)
  • 2 – Room air sensor fault (Rank 3)
  • 3 – Indoor coil sensor fault (Rank 4)
  • 8 – Indoor fan motor fault (Rank 5)
  • Continuous – Indoor sensor wiring reversed (test mode) (Rank 6)

R-32 ductless (newer models) — 4-character codes

Models: 42QHG, 38QHG, 40MBAB, 38MAR, 40MAR, Carrier R32

How to read: Newer R-32 units show 4-character codes (EH/EL/EC/PC). Many display briefly as 2 characters then 2 more, or show via the remote: press LED/Display 4 times (or 'Self Clean'/'Turbo' combinations on some remotes) to show the full code. The legacy 2-character equivalents are shown on older models.

  • EH00 – Indoor EEPROM parameter error (Operation 1 flash)
  • EH0A – Indoor EEPROM parameter error
  • EL01 – Indoor–outdoor communication error (Operation 2 flashes)
  • EH02 – Zero-crossing signal detection error
  • EH03 – Indoor fan speed outside normal range (Operation 4 flashes)
  • EH60 – Indoor room temperature sensor (T1) open/short (Operation 6 flashes)
  • EH61 – Evaporator coil sensor (T2) open/short (Operation 6 flashes)
  • EL0C – Refrigerant leak detection (Operation 8 flashes)
  • EH0b – Communication error between indoor main board and display (Operation 9 flashes)
  • EH0E – Water-level alarm (Operation 13 flashes)
  • EC51 – Outdoor EEPROM parameter error
  • EC52 – Condenser coil sensor (T3) open/short
  • EC53 – Outdoor ambient sensor (T4) open/short
  • EC54 – Discharge sensor (TP) open/short
  • EC56 – Evaporator outlet sensor (T2B) open/short (multi)
  • EC07 – Outdoor fan speed outside normal range
  • EC0d – Outdoor unit malfunction
  • PC00 – IPM malfunction or IGBT overcurrent protection
  • PC01 – Over-voltage or under-voltage protection
  • PC02 – Compressor top / IPM high temperature protection
  • PC03 – High or low pressure protection
  • PC04 – Inverter compressor drive error
  • PC08 – Outdoor current overload protection
  • PC40 – Communication error between outdoor main chip and compressor driven chip
  • LC06 – Low ambient / anti-cold protection

VRF indoor units (40VMI / 40VM series) & wired controller

Models: 40VMI, 40VM, 40VMC, 40VMD, 40VMW, 38VMA, 38VR, XCT, Carrier VRF

How to read: Codes show on the indoor display / wired controller. Outdoor (38VMA) codes show on the outdoor PCB digital display — see the 38VMA service manual.

  • E0 – Heating/cooling mode conflict
  • E1 – Communication error between indoor and outdoor unit
  • E2 – Indoor room temperature sensor (T1) error
  • E4 – Evaporator outlet temperature sensor (T2B) error
  • E5 – Evaporator temperature sensor (T2A) error
  • E6 – Indoor DC fan error
  • E7 – EEPROM error (data storage)
  • E9 – Communication error between indoor unit and wired controller
  • Eb – Indoor EEV error
  • Ed – Outdoor unit error — check outdoor display
  • EE – Condensate overflow (water level)
  • FE – No address on first power-up — address the system
  • UU – MDC in auto system-check mode

MIDEA (& OEM BRANDS)

Midea-platform wall, cassette & ducted splits — legacy codes (Midea, Bosch, Pioneer, MRCOOL, Koppel)

Models: 42Q, 38Q, 42QHC, 42QHB, 38QHC, 40VC, 40MBAB, MSAF, MSMB, MSAG, MS, MOB, MOD, MBT, MTI, Xpower, Midea, Carrier, Pioneer, Bosch Climate

How to read: Code shows on the indoor display. Units without a display flash the Operation lamp (indoor faults, Timer OFF) or Operation lamp with Timer ON (outdoor sensor faults) — count the flashes. Timer-lamp-only flashes indicate P-codes (outdoor protection).

  • E0 – Indoor EEPROM parameter error (Operation lamp 1 flash)
  • E1 – Indoor–outdoor communication error (Operation lamp 2 flashes)
  • E2 – Zero-crossing signal detection error (Operation lamp 3 flashes)
  • E3 – Indoor fan speed out of control (Operation lamp 4 flashes)
  • E4 – Indoor room temperature sensor (T1) open/short (Operation lamp 5 flashes)
  • E5 – Evaporator coil sensor (T2) open/short (Operation lamp 6 flashes)
  • E7 – Indoor PCB–display board communication error
  • EC – Refrigerant leak detected (T2 not dropping in cooling) (Operation lamp 7 flashes)
  • EE – Water-level alarm (cassette/ducted) (Operation lamp 8 flashes)
  • F0 – Overload current protection (Operation 1 flash, Timer ON)
  • F1 – Outdoor ambient sensor (T4) open/short (Operation 2, Timer ON)
  • F2 – Condenser coil sensor (T3) open/short (Operation 3, Timer ON)
  • F3 – Discharge temperature sensor (T5) open/short (Operation 4, Timer ON)
  • F4 – Outdoor EEPROM parameter error (Operation 5, Timer ON)
  • F5 – Outdoor fan speed out of control (Operation 6, Timer ON)
  • F6 – Evaporator outlet sensor (T2B) open/short (Operation 7, Timer ON)
  • P0 – IPM malfunction or IGBT overcurrent protection (Timer lamp 1 flash)
  • P1 – Over-voltage or under-voltage protection (Timer lamp 2 flashes)
  • P2 – Compressor top / IPM high temperature protection (Timer lamp 3 flashes)
  • P3 – Low outdoor ambient temperature protection (Timer lamp 4 flashes)
  • P4 – Inverter compressor drive error (Timer lamp 5 flashes)
  • P6 – Compressor voltage protection / high-low pressure (Timer lamp 7 flashes)
  • CP – Remote on/off terminal open circuit

Midea-platform R-32 models — 4-character codes

Models: MSAG, MSCE, MSAFG, 42QHG, 38QHG, Breezeless, Xtreme Save, Carrier R32

How to read: Newer R-32 units show 4-character codes (EH/EL/EC/PC). Many display briefly as 2 characters then 2 more, or show via the remote: press LED/Display 4 times (or 'Self Clean'/'Turbo' combinations on some remotes) to show the full code. The legacy 2-character equivalents are shown on older models.

  • EH00 – Indoor EEPROM parameter error (Operation 1 flash)
  • EH0A – Indoor EEPROM parameter error
  • EL01 – Indoor–outdoor communication error (Operation 2 flashes)
  • EH02 – Zero-crossing signal detection error
  • EH03 – Indoor fan speed outside normal range (Operation 4 flashes)
  • EH60 – Indoor room temperature sensor (T1) open/short (Operation 6 flashes)
  • EH61 – Evaporator coil sensor (T2) open/short (Operation 6 flashes)
  • EL0C – Refrigerant leak detection (Operation 8 flashes)
  • EH0b – Communication error between indoor main board and display (Operation 9 flashes)
  • EH0E – Water-level alarm (Operation 13 flashes)
  • EC51 – Outdoor EEPROM parameter error
  • EC52 – Condenser coil sensor (T3) open/short
  • EC53 – Outdoor ambient sensor (T4) open/short
  • EC54 – Discharge sensor (TP) open/short
  • EC56 – Evaporator outlet sensor (T2B) open/short (multi)
  • EC07 – Outdoor fan speed outside normal range
  • EC0d – Outdoor unit malfunction
  • PC00 – IPM malfunction or IGBT overcurrent protection
  • PC01 – Over-voltage or under-voltage protection
  • PC02 – Compressor top / IPM high temperature protection
  • PC03 – High or low pressure protection
  • PC04 – Inverter compressor drive error
  • PC08 – Outdoor current overload protection
  • PC40 – Communication error between outdoor main chip and compressor driven chip
  • LC06 – Low ambient / anti-cold protection

KELVINATOR

Kelvinator inverter split (KSV / KSD) — Midea-platform codes

Models: KSV, KSD, KSV26, KSV35, KSV53, KSV62, KSV70, KSV80, KSD25, KSD50, KSD80

How to read: Code shows on the indoor display. Electrolux lists E0, E1, E2, P1, P2, P3, F1, F2, F3 and EC as self-diagnostic codes. If a code persists after switching off for 10 minutes and restarting, the system needs service. Confirm against the Electrolux diagnostic manual for the model (e.g. KSSSI90 / KSSSI113).

  • E0 – Indoor EEPROM parameter error (Operation lamp 1 flash)
  • E1 – Indoor–outdoor communication error (Operation lamp 2 flashes)
  • E2 – Zero-crossing signal detection error (Operation lamp 3 flashes)
  • E3 – Indoor fan speed out of control (Operation lamp 4 flashes)
  • E4 – Indoor room temperature sensor (T1) open/short (Operation lamp 5 flashes)
  • E5 – Evaporator coil sensor (T2) open/short (Operation lamp 6 flashes)
  • E7 – Indoor PCB–display board communication error
  • EC – Refrigerant leak detected (T2 not dropping in cooling) (Operation lamp 7 flashes)
  • EE – Water-level alarm (cassette/ducted) (Operation lamp 8 flashes)
  • F0 – Overload current protection (Operation 1 flash, Timer ON)
  • F1 – Outdoor ambient sensor (T4) open/short (Operation 2, Timer ON)
  • F2 – Condenser coil sensor (T3) open/short (Operation 3, Timer ON)
  • F3 – Discharge temperature sensor (T5) open/short (Operation 4, Timer ON)
  • F4 – Outdoor EEPROM parameter error (Operation 5, Timer ON)
  • F5 – Outdoor fan speed out of control (Operation 6, Timer ON)
  • F6 – Evaporator outlet sensor (T2B) open/short (Operation 7, Timer ON)
  • P0 – IPM malfunction or IGBT overcurrent protection (Timer lamp 1 flash)
  • P1 – Over-voltage or under-voltage protection (Timer lamp 2 flashes)
  • P2 – Compressor top / IPM high temperature protection (Timer lamp 3 flashes)
  • P3 – Low outdoor ambient temperature protection (Timer lamp 4 flashes)
  • P4 – Inverter compressor drive error (Timer lamp 5 flashes)
  • P6 – Compressor voltage protection / high-low pressure (Timer lamp 7 flashes)
  • CP – Remote on/off terminal open circuit

GREE

Inverter wall split, U-Match ducted/cassette & Free Match

Models: GWH, GWC, GUD, GKH, GTH, GFH, GU, GMV, Lomo, Pular, Fairy, U-Match, Free Match, Hansol, XK, XE72

How to read: Code shows on the indoor display or wired controller (XK/XE series). Without a display, count RUN/COOL/HEAT LED flashes (see service manual). Some remotes show codes by pressing Light 4 times within 3 s.

  • E1 – System high pressure protection (RUN LED 1 flash)
  • E2 – Indoor anti-freeze protection (RUN LED 2 flashes)
  • E3 – Low pressure / refrigerant shortage protection (RUN LED 3 flashes)
  • E4 – Compressor discharge high temperature protection (RUN LED 4 flashes)
  • E5 – AC overcurrent protection (RUN LED 5 flashes)
  • E6 – Indoor–outdoor communication error (RUN LED 6 flashes)
  • E7 – Mode conflict (multi)
  • E8 – High temperature / overload protection (RUN LED 8 flashes)
  • E9 – Anti-cold air (heating) / water-full protection (cassette)
  • EE – Outdoor EEPROM error
  • EU – IPM / heatsink high temperature frequency limiting
  • F0 – System low refrigerant / blockage protection
  • F1 – Indoor ambient (return air) sensor open/short
  • F2 – Indoor coil (evaporator) sensor open/short
  • F3 – Outdoor ambient sensor open/short
  • F4 – Outdoor coil (condenser) sensor open/short
  • F5 – Outdoor discharge sensor open/short
  • F6 – Overload frequency limiting / reduction
  • F8 – Overcurrent frequency limiting / reduction
  • F9 – High discharge temperature frequency limiting
  • FH – Anti-freezing frequency limiting
  • H1 – Defrosting (normal)
  • H3 – Compressor overload protection (OLP)
  • H4 – System abnormal / overload
  • H5 – IPM protection
  • H6 – No feedback from indoor fan (PG) motor (Indicator 11 flashes)
  • H7 – Compressor desynchronisation
  • HC – PFC protection
  • L3 – Outdoor DC fan motor error
  • L9 – Over-power protection
  • LP – Indoor/outdoor unit capacity mismatch (on GMV VRF: PG motor zero-crossing fault)
  • Lc – Compressor start failure
  • P5 – Compressor overcurrent
  • P7 – Heatsink sensor error
  • P8 – IPM / heatsink high temperature
  • PH – DC bus high voltage
  • PL – DC bus low voltage
  • PU – Capacitor charging error
  • U1 – Compressor phase current detection error
  • U3 – DC bus voltage drop
  • U5 – Whole unit current detection error
  • U7 – 4-way valve reversing abnormal
  • U8 – Zero-cross detection (input power) circuit malfunction (Indicator 17 flashes)
  • C5 – Jumper cap (model jumper) error (Indicator 15 flashes)
  • b5 – Indoor inlet tube sensor open/short (Indicator 19 flashes)

HAIER

Inverter wall split (AS / HSU / Flexis / Tempo / Pearl)

Models: AS, HSU, 1U, AS25, AS35, AS50, AS71, AD, AB, Flexis, Tempo, Pearl, Nebula

How to read: Code shows on the indoor display. Outdoor faults also flash LED1 on the outdoor PCB (count flashes).

  • E1 – Indoor room temperature sensor fault
  • E2 – Indoor heat exchanger (coil) sensor fault
  • E4 – Indoor EEPROM error
  • E7 – Indoor–outdoor communication fault (Outdoor LED1 15 flashes)
  • E9 – Indoor unit overload in heating / high work-intensity protection
  • E14 – Indoor fan motor malfunction
  • F1 – IPM protection (Outdoor LED1 2 flashes)
  • F2 – Compressor overcurrent (Outdoor LED1 24 flashes)
  • F3 – Communication error between power module and main PCB
  • F4 – Compressor discharge temperature protection
  • F12 – Outdoor EEPROM error (Outdoor LED1 1 flash)
  • F13 – Lack of refrigerant (Outdoor LED1 16 flashes)
  • F14 – 4-way valve reverse failure (Outdoor LED1 17 flashes)
  • F19 – Power supply over/under voltage protection (Outdoor LED1 6 flashes)
  • F20 – Compressor overload / high pressure protection (Outdoor LED1 5 flashes)
  • F21 – Outdoor defrost (coil) sensor fault (Outdoor LED1 10 flashes)
  • F6 – Outdoor ambient temperature sensor fault (Outdoor LED1 12 flashes)
  • F7 – Suction temperature sensor fault (Outdoor LED1 11 flashes)
  • F8 – Outdoor DC fan motor fault (Outdoor LED1 9 flashes)
  • F11 – Compressor running abnormally / jammed (Outdoor LED1 18 flashes)
  • F25 – Discharge (exhaust) temperature sensor fault (Outdoor LED1 13 flashes)
  • F22 – Outdoor AC overcurrent protection (Outdoor LED1 3 flashes)
  • F23 – Compressor phase (V-phase) overcurrent protection (Outdoor LED1 25 flashes)
  • F27 – Compressor locked / current sampling circuit fault (Outdoor LED1 7 flashes)
  • F28 – Compressor position detection circuit fault
  • F35 – Compressor driver board failure
  • F43 – Model matching abnormality
  • FE – Refrigerant leak detection malfunction

HITACHI

Residential wall split (RAK / RAC / RAS-…FH) — timer lamp codes

Models: RAK, RAC, RAS-FH, RAS-25FH, RAS-35FH, Performance, Premium, Summit, Airhome

How to read: Indoor TIMER lamp flashes a number of times, pauses and repeats — count the flashes. TIMER flashing steadily 1 s on / 1 s off in heating is coil pre-heat, not a fault. If the indoor FILTER lamp flashes 4 times it is an outdoor fault: count flashes on outdoor PCB LED LD301 (LD304 flashing = comms error with that indoor circuit on multi). Confirm against the model's service manual — tables vary by generation.

  • Timer 1s on/off – Coil pre-heat in heating mode — not a fault
  • 01 – Indoor coil too warm in cooling or too cold in heating — reversing valve or coil thermistor faulty (Timer lamp 1 flash)
  • 02 – Forced operation from outdoor unit — not a fault (Timer lamp 2 flashes)
  • 03 – Communication error — faulty wiring, indoor or outdoor PCB (Timer lamp 3 flashes)
  • 04 – Outdoor unit fault — read outdoor LED LD301 flash count (Timer lamp 4 flashes / filter lamp 4 flashes)
  • 06 – Float switch activated (drain) (Timer lamp 6 flashes)
  • 07 – Drain pump forced operation — drain test switch left in test position or PCB fault (Timer lamp 7 flashes)
  • 08 – Louvre not opening — louvre motor, microswitch or PCB (RAF units only) (Timer lamp 8 flashes)
  • 09 – Indoor thermistor fault — air inlet or coil thermistor open/short or PCB (Timer lamp 9 flashes)
  • 13 – EEPROM data error — faulty PCB (Timer lamp 13 flashes)

Utopia / Set Free / Primairy commercial — alarm codes

Models: RAS-, RPI, RCI, RCD, RPK, RPC, RPF, RAD, Utopia, Set Free, Primairy, PC-ARF, PC-ART, PC-P2HTE

How to read: Alarm code shows on the wired controller (PC-ARF/ART) with the unit and refrigerant cycle number. Outdoor 7-segment display gives the same code.

  • 01 – Indoor protection device activated (float switch / drain)
  • 02 – Outdoor protection device activated (high pressure cut or compressor high temperature cut)
  • 03 – Indoor–outdoor transmission abnormality
  • 04 – Inverter–outdoor PCB transmission abnormality
  • 05 – Power supply phase abnormality (reverse / open phase)
  • 06 – Abnormal inverter voltage (excessively low or high)
  • 07 – Decrease in discharge superheat (overcharge / EEV open lock)
  • 08 – High discharge gas temperature (undercharge / leak / EEV closed)
  • 09 – Outdoor fan motor protection
  • 11 – Indoor inlet air thermistor
  • 12 – Indoor outlet air thermistor
  • 13 – Indoor freeze protection (liquid pipe) thermistor
  • 14 – Indoor gas pipe thermistor
  • 19 – Indoor fan motor protection
  • 20 – Compressor top (discharge) thermistor
  • 21 – High pressure sensor
  • 22 – Outdoor ambient thermistor
  • 24 – Outdoor heat exchanger liquid pipe (evaporating) thermistor
  • 31 – Incorrect capacity setting / combination
  • 35 – Incorrect indoor unit number setting
  • 41 – Cooling overload (high pressure)
  • 42 – Heating overload (high pressure)
  • 47 – Low suction pressure protection
  • 48 – Inverter overcurrent protection
  • 51 – Inverter current sensor abnormality
  • 53 – Inverter module (ISPM) protection
  • 54 – Inverter fin temperature increase
  • 57 – Fan controller abnormality
  • EE – Compressor protection (repeated alarms)

TEMPERZONE

UC7 / UC8 controlled splits & packages (OSA, OPA, ISD, OSI)

Models: OSA, OPA, ISD, OSI, OPH, ISH, MWR, MWU, UC7, UC8, SAT-3, TZT-100, RKS, RKTG, RKSG

How to read: Fault messages and codes show on the UC7/UC8 controller display on the outdoor/package unit, and on compatible room thermostats (SAT-3, TZT-100). Inverter units also show inverter fault codes — see the UC8 troubleshooting guide.

  • LP – Low pressure protection active
  • HP – High pressure protection active
  • HI-t – High (discharge) temperature protection active
  • FROSt – Indoor coil frost protection active
  • HI-SL – High suction line temperature protection active
  • Lo-dSH – Low discharge superheat protection active
  • Hi-dSH – High discharge superheat protection active
  • OL – Overload protection active (IN #2 open circuit)
  • F10 – Outdoor fan fault (no serial communication)
  • F11 – Indoor fan fault (no serial communication)
  • F12 – Low pressure transducer fault (shows as LP)
  • F13 – High pressure transducer fault (shows as HP)
  • F14 – Suction line temperature sensor fault (SL)
  • F15 – Discharge line temperature sensor fault (DL)
  • F16 – De-ice temperature sensor fault (DEI)
  • F17 – Outdoor coil temperature sensor fault (OC)
  • F18 – Indoor coil temperature sensor fault (IC)
  • F19 – Ambient temperature sensor fault (AMB)
  • F20 – Superheat unknown

Need a licensed technician? Total Cooling Services Qld — Moreton Bay, Sunshine Coast to Gympie and surrounds. Call 07 3112 7566. QBCC 15142132. Brand names are trademarks of their owners and are used for identification only. Diagnostic work must be carried out by licensed technicians.